Figure 42Q(V) Volt-Var Function
Q The Conext XW Pro output reactive power in percentage of nominal rated apparent
power Sn.
For example, Q1 = 44% means Q1=2640 VAr for Sn=6000 kVA of the Conext XW Pro
nominal rated apparent power.
V - Utility grid voltage in percentage) of nominal voltage Vn
For example, V1 = 94% means V1=225.6 V for 240 V nominal grid.
Parameter
Voltage [%Vn] Reactive Power [%Sn]
Default Range Default Range
Vref 100 95 to 105 N/A N/A
Point P1 Vref - 6 82 to (V2-2) 44 0 to +100
Point P2 Vref - 3 (Vref-3) to Vref 0 0
Point P3 Vref - 2 (Vref-3) to Vref 0 0
Point P4 Vref + 2 100 to (Vref+3) 0 0
Point P5 Vref + 3 100 to (Vref+3) 0 0
Point P6 Vref + 6 (V3+2) to 118 -44 -100 to 0
Table 40HECO Q(V) Volt-Var function default and adjustability range settings
The Reactive Power Volt-Var function has priority over generated active power. The
Conext XW Pro may need to reduce produced active power to meet the reactive power
demand.
Fixed Power Factor Function
This function allows the user to set the Conext XW Pro output Power Factor in Grid
Support Mode.
n The Power factor (PF)is controllable from 20% to 100% nominal output power and
default setting is PF = 0.95 leading.