n Power Factor setting adjustability range from with an adjustability range from - 0.85
lagging to 0.85 leading (EEI
3
Power Factor sign convention).
n When enabled, the PF setting has priority over other functions, which means that
active power may be reduced to achieve the power factor setpoint.
The Fixed Power Factor function is disabled by default.
Figure 43Fixed Power Factor function
Parameter Default Range Observations
Power Factor 0.95 leading
1
EEI Generator reference
frame convention
2
(-0.85 to -0.99) lagging
(0.85 to 0.99) leading
Table 41HECO Fixed Power Factor Function default and adjustability range settings
3
EEI Edison Electric Institute
2
EEI - Edison Electric Institute
Specifications Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 145