P(V) Volt-Watt Function
When the Conext XW Pro is in Grid Support mode and P(V) function is enabled:
n The Conext XW Pro dynamically increases the active power injected into the utility
grid from the pre-disturbance level when AC voltage trends lower than V2, following
the P1P2 segment in the figure below.
n The Conext XW Pro dynamically curtails active power injected into the utility grid
from the pre-disturbance level when AC voltage trends higher than V5, following
P5P6 segment in the figure below.
n By adjusting the active power in response to grid voltage fluctuations, Conext XW
Pro contributes to grid stabilization towards the nominal value.
The P(V) function is disabled by default.
Figure 44P(V) Volt-Watt Function
P The Conext XW Pro output active power in percentage of nominal rated active power
Pn.
V - Utility grid voltage in percentage) of nominal voltage Vn
For example, V1 = 90% means V1=216 V for Vn = 240 V nominal grid.
Parameter
Voltage [% Vn] Active Power [%Pn]
Default Range Default Range
Point P1 90 90 to 94 100 0 to 100
Point P2 94 91 to 95 0 0
Point P3 95 91 to 96 0 0
Point P4 105 104 to 109 0 0
Point P5 106 105 to 109 0 0
Point P6 110 106 to 110 -100 -100 to 0
Table 42HECO P(V) Volt-Watt function default and adjustability range
settings
Conext XW Pro Owner's Guide Specifications