Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
HVRT
Time [s] Voltage [%Vn]
Default Range Default Range
Point P1.H 0.16 N/A 120 N/A
Point P2.H 1 1 to 13 120 N/A
Point P3.H 1 1 to 13 110 110 to 120
Table 44HECO High Voltage Ride-through (HVRT) default and adjustability range
settings
LVRT
Time [s] Voltage [%Vn]
Default Range Default Range
Point P1.L 2 0.5 to 21 50 N/A
Point P2.L 11 11 to 50 50 N/A
Point P3.L 11 11 to 50 70 50 to 88
Point P4.L 21 21 to 50 70 50 to 88
Point P5.L 21 21 to 50 88 50 to 88
Table 45HECO Low Voltage Ride-through (LVRT) default and adjustability range
settings
Frequency Ride-Through (FRT)
The Conext XW Pro has the capability of remaining connected to the utility grid and
operational for defined time intervals (ride-through) while AC frequency deviates from
nominal range, as seen in the figure below.
n At the end of ride-through time, if the utility grid frequency has not recovered to the
normal range, the Conext XW Pro will disconnect and transition to Inverter (Grid-
Forming) Mode.
Frequency Ride-through is enabled by default.
Figure 47High/Low Frequency Ride-through (HFRT/LFRT) regions
Specifications Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 149