n When in the Under Frequency 1 (UF2) or Over Frequency 2 (OV2) regions, the
Conext XW Pro goes into Permissive Operation (i.e. it may operate at any current
level during ride-through time).
n While in the Under Frequency 1 (UF1) or Over Frequency 1 (OF1), the Conext XW
Pro goes into Mandatory Operation (i.e. generates an output current greater than or
equal to 80% of pre-disturbance current value).
n When in the Continuous Operation region (CO), the Conext XW Pro operates
indefinitely without tripping.
HVRT
Time [s] Frequency [Hz]
Default Range Default Range
Point P1.H 0.16 0.16 to 1000 64 62 to 66
Point P2.H 21 21 to 1000 64 62 to 66
Point P3.H 21 21 to 1000 63 61 to 66
Table 46HECO (Oahu, Maui, Hawaii Island) High Frequency Ride-through (HFRT)
default and adjustability range settings
LVRT
Time [s] Frequency [Hz]
Default Range Default Range
Point P1.L 0.16 0.16 to 1000 56 50 to 57
Point P2.L 21 21 to 1000 56 50 to 57
Point P3.L 21 21 to 1000 57 50 to 59
Table 47HECO (Oahu, Maui, Hawaii Island) Low Frequency Ride-through (LFRT)
default and adjustability range settings
HVRT
Time [s] Voltage [%Vn]
Default Range Default Range
Point P1.H 0.16 0.16 to 1000 65 62 to 66
Point P2.H 21 21 to 1000 65 62 to 66
Point P3.H 21 21 to 1000 63 61 to 66
Table 48HECO (Molokai and Lanai) High Frequency Ride-through (HFRT) default and
adjustability range settings
LVRT
Time [s] Voltage [%Vn]
Default Range Default Range
Point P1.L 0.16 0.16 to 1000 50 50 to 57
Point P2.L 21 21 to 1000 50 50 to 57
Point P3.L 21 21 to 1000 57 50 to 59
Table 49HECO (Molokai and Lanai) Low Frequency Ride-through (LFRT) default and
adjustability range settings
Conext XW Pro Owner's Guide Specifications