Conext XW PRO 6848 6,800W 48V Installation
Table Of Contents
- Safety Information
- Label Symbols
- Product Labels
- Radio Frequency Interference Notices
- Audience
- About
- Product Safety Information
- Introduction
- Monitoring Operation
- External Monitoring Control
- Configuration
- Troubleshooting
- Specifications
- Electrical Specifications
- Mechanical Specifications
- Regulatory Approvals
- Grid Support Utility Interactive Functions
- California Rule 21: Smart Inverter Grid-Support Utility Interactive Functions
- Hawaiian Electric Company (HECO) Rule No. 14: Smart Inverter Grid-Support Uti...
- IEEE 1547-2003 Standard for Interconnecting Distributed Resources with Electr...
- Puerto Rico Energy Power Authority (PREPA) Technical Requirements for Interco...
- Defaults
Point P1 92 85 to 98.75 30 +15 to +60
Point P2 96.7 90 to 100 0 0
Point P3 97 90 to 100 0 0
Point P4 103 100 to 110 0 0
Point P5 103.3 100 to 110 0 0
Point P6 107 101.25 to 112.5 -30 -60 to -15
Fixed Power Factor Function
This function allows the user to set the Conext XW Pro output Power Factor in Grid
Support Mode.
n The Power factor (PF)is controllable from 20% to 100% nominal output power.
n Default setting is PF = 0.95 leading.
n Power Factor setting adjustability range from - 0.85 lagging to 0.85 leading (EEI
4
Power Factor sign convention).
n When enabled, the PF setting has priority over other functions, which means that
active power may be reduced to achieve the power factor setpoint.
The Fixed Power Factor function is disabled by default.
Figure 51Fixed Power Factor function
Parameter Default Range Observations
Table 55IEEE1547-2003 Fixed Power Factor Function default and adjustability range
settings
4
EEI – Edison Electric Institute
Specifications Conext XW Pro Owner's Guide