P(V) Volt-Watt Function
When the Conext XW Pro is in Grid Support mode and P(V) function is enabled:
n The Conext XW Pro dynamically increases the active power injected into the utility
grid when AC voltage trends lower than V2 following P1P2 segment in the figure
below.
n The Conext XW Pro dynamically curtails active power injected into the utility grid
when AC voltage trends higher than V5, following P5P6 segment in in the figure
below.
The P(V) function is disabled by default.
Figure 52P(V) Volt-Watt Function
P The Conext XW Pro output active power in percentage of nominal rated active power
Pn.
V - Utility grid voltage in percentage) of nominal voltage Vn
For example, V1 = 90% means V1=216 V for Vn = 240 V nominal grid.
Parameter
Voltage [% Vn] Active Power [%Pn]
Default Range Default Range
Point P1 90 85 to 99 100 0 to 100
Point P2 94 90 to 99 0 0
Point P3 95 90 to 100 0 0
Point P4 105 100 to 110 0 0
Point P5 106 101 to 110 0 0
Point P6 110 101 to 115 -100 -100 to 0
Table 56IEEE1547-2003 P(V) Volt-Watt function default and
adjustability range settings
NOTE: If both P(V) and P(f) are active, the lesser of the two power levels will take
precedence (i.e. the curve that is curtailing the active power the most will set the output
power level).