Parameter
Frequency [Hz] Active Power [%Pn]
Default Range Default Range
Point P1 48 46 to 49 100 0 to 100
Point P2 49.96 49 to 49.96 0 0
Point P3 49.98 49 to 50 0 0
Point P4 50.02 50 to 51 0 0
Point P5 50.04 50.04 to 51 0 0
Point P6 52 51 to 54 -100 -100 to 0
Table 58IEEE1547-2003 P(f) Frequency-Watt function default and adjustability
range settings 50 Hz
NOTE: If both P(V) and P(f) are active then the lesser of the two power levels shall take
precedence (i.e. the curve that is curtailing the active power the most shall set the output
power level)
Voltage Ride Through (VRT)
The Conext XW Pro has the capability of remaining connected to the utility grid and
operational for defined time intervals (ride-through) while AC voltage deviates from the
nominal range, as shown in the figure below. At the end of ride-through time, if the utility
grid voltage has not recovered to normal range, the Conext XW Pro will disconnect and
transition to Inverter (Grid-Forming) Mode.
Voltage Ride-through is disabled by default.
Figure 54High/Low Voltage Ride-through (HVRT/LVRT) regions
n When in the Continuous Operation region (Near Nominal), the Conext XW Pro
operates indefinitely without tripping.
n When in Low-Voltage 1 (LV1) or Low-Voltage 2 (LV2), the Conext XW Pro goes into
Mandatory Operation (i.e. generates an output current greater than or equal to 80% of
pre-disturbance current value).
Specifications Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 161