Anti-Islanding
Disconnect
Under
Voltage L-N
Slow
The line-to-neutral voltage below which the Conext XW Pro will stop export
of power and record an islanding fault. The default value for this setting is
105.6 V, and the disconnect will occur if the inverter is under frequency for
0.5 second.
Anti-Islanding
Disconnect
Under
Voltage L1-L2
Fast
The line-to-line voltage below which the Conext XW Pro will stop export of
power and record an islanding fault. The default value for this setting is 132
V.
Anti-Islanding
Disconnect
Under
Voltage L1-L2
Slow
The line-to-line voltage below which the Conext XW Pro will stop export of
power and record an islanding fault. The default value for this setting is
211.2 V, and the disconnect will occur if the inverter is under frequency for
0.5 second.
Transient
Over-Voltage
(TrOV) trip
time
The disconnection time delay for the grid voltage exceeding the TrOV Trip
level. The default value for this setting is 0.016 seconds.
Transient
Over-Voltage
(TrOV) trip
level
When Transient Over-Voltage is enabled, grid voltage in percentage of
nominal value [%Vn], above which the Conext XW Pro will stop operating
after the TrOV trip time. The default value is 120 [%Vn].
Parameter Default Range Unit
Anti-Islanding Disconnect Slow Delay 0.5 0.2 to 10 [s]
Anti-Islanding Disconnect Over Frequency 60.5 60.1 to 67 [Hz]
Anti-Islanding Disconnect Under Frequency 59.3 53 to 59.9 [Hz]
Anti-Islanding Disconnect Over Voltage LN Fast 135 132 to 150 [V]
Anti-Islanding Disconnect Over Voltage LN Slow 132 120 to 138 [V]
Anti-Islanding Disconnect Over Voltage L1L2 Fast 270 234 to 300 [V]
Anti-Islanding Disconnect Over Voltage L1L2 Slow 264 240 to 276 [V]
Anti-Islanding Disconnect Under Voltage LN Fast 66 0 to 96 [V]
Anti-Islanding Disconnect Under Voltage LN Slow 105.6 60 to 108 [V]
Anti-Islanding Disconnect Under Voltage L1L2 Fast 132 0 to 192 [V]
Anti-Islanding Disconnect Under Voltage L1L2 Slow 211.2 120 to 216 [V]
TrOV trip time 16 10 to 200 [ms]
TrOV trip level 120 100 to 150 [%Vn]
Table 66IEEE1547-2003 Grid Disconnect default and adjustability range settings 60
Hz
Conext XW Pro Owner's Guide Specifications