Conext XW PRO 6848 6,800W 48V Installation
Table Of Contents
- Safety Information
- Label Symbols
- Product Labels
- Radio Frequency Interference Notices
- Audience
- About
- Product Safety Information
- Introduction
- Monitoring Operation
- External Monitoring Control
- Configuration
- Troubleshooting
- Specifications
- Electrical Specifications
- Mechanical Specifications
- Regulatory Approvals
- Grid Support Utility Interactive Functions
- California Rule 21: Smart Inverter Grid-Support Utility Interactive Functions
- Hawaiian Electric Company (HECO) Rule No. 14: Smart Inverter Grid-Support Uti...
- IEEE 1547-2003 Standard for Interconnecting Distributed Resources with Electr...
- Puerto Rico Energy Power Authority (PREPA) Technical Requirements for Interco...
- Defaults
Parameter Default Range Unit
Anti-Islanding Disconnect Slow Delay 0.5 0.2 to 10 [s]
Anti-Islanding Disconnect Over Frequency 50.5 50.1 to 57 [Hz]
Anti-Islanding Disconnect Under Frequency 49.3 43 to 49.9 [Hz]
Anti-Islanding Disconnect Over Voltage LN Fast 135 132 to 150 [Vrms]
Anti-Islanding Disconnect Over Voltage LN Slow 132 120 to 138 [Vrms]
Anti-Islanding Disconnect Over Voltage L1L2 Fast 270 234 to 300 [Vrms]
Anti-Islanding Disconnect Over Voltage L1L2 Slow 264 240 to 276 [Vrms]
Anti-Islanding Disconnect Under Voltage LN Fast 66 0 to 96 [Vrms]
Anti-Islanding Disconnect Under Voltage LN Slow 105.6 60 to 108 [Vrms]
Anti-Islanding Disconnect Under Voltage L1L2 Fast 132 0 to 192 [Vrms]
Anti-Islanding Disconnect Under Voltage L1L2 Slow 211.2 120 to 216 [Vrms]
TrOV trip time 16 10 to 200 [ms]
TrOV trip level 120 100 to 150 [%Vn]
Table 67 IEEE1547-2003 Grid Disconnect default and adjustability range settings – 50
Hz
Grid Reconnect Settings
At initial start-up or upon disconnection, the Conext XW Pro will remain offline until the
voltage and frequency are within the qualified range (i.e. less than Over
Voltage/Frequency limit and higher than Under Voltage/Frequency limit).
Parameter Default Range Unit
Anti-Islanding Reconnect Time 300 0 to 300 [s]
HF Reconnect Frequency 60.5 60.1 to 61 [Hz]
LF Reconnect Frequency 59.3 58 to 59.9 [Hz]
HV Reconnect Nominal Voltage 105.83 100 to 110 [%Vn]
LV Reconnect Nominal Voltage 88.33 88 to 100 [%Vn]
Table 68IEEE1547-2003 Grid Reconnection default and adjustability range settings – 60
Hz
Parameter Default Range Unit
Anti-Islanding Reconnect Time 300 0 to 300 [s]
HF Reconnect Frequency 50.5 50.1 to 51 [Hz]
LF Reconnect Frequency 49.3 48 to 49.9 [Hz]
HV Reconnect Nominal Voltage 105.83 100 to 110 [%Vn]
LV Reconnect Nominal Voltage 88.33 88 to 100 [%Vn]
Table 69IEEE1547-2003 Grid Reconnection default and adjustability range settings – 50
Hz
Specifications Conext XW Pro Owner's Guide