Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Figure 58Q(V) Volt-Var Function
Q The Conext XW Pro output reactive power in percentage of nominal rated apparent
power Sn.
For example, Q1 = 30% means Q1=1800 VAr for Sn=6000 kVA of the Conext XW Pro
nominal rated apparent power.
V - Utility grid voltage in percentage) of nominal voltage Vn
For example, V1 = 92% means V1=221 V for 240 V nominal grid.
Parameter
Voltage [%Vn] Reactive Power [%Sn]
Default Range Default Range
Point P1 92 85 to 98.75 30 +15 to +60
Point P2 96.7 90 to 100 0 0
Point P3 97 90 to 100 0 0
Point P4 103 100 to 110 0 0
Point P5 103.3 100 to 110 0 0
Point P6 107 101.25 to 112.5 -30 -60 to -15
Table 70PREPA Q(V) Volt-Var function default and adjustability range settings
The Reactive Power Volt-Var function has priority over generated active power. The
Conext XW Pro may need to reduce produced active power to meet the reactive power
demand.
Fixed Power Factor Function
This function allows the user to set the Conext XW Pro output Power Factor in Grid
Support Mode.
n The Power Factor (PF)is controllable from 20% to 100% nominal output power and
default setting is PF = 0.95 leading.
Specifications Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 171