NOTE: If both P(V) and P(f) are active, the lesser of the two power levels will take
precedence (i.e. the curve that is curtailing the active power the most will set the output
power level).
P(f) Frequency-Watt Function
When the Conext XW Pro is in Grid Support mode and P(f) function is enabled:
n The Conext XW Pro dynamically increases the active power injected into the grid
from the pre-disturbance level when AC frequency trends lower than f2, following the
P1P2 segment in the figure below.
n The Conext XW Pro dynamically curtails active power injected into utility grid from
the pre-disturbance level when AC frequency trends higher than f5 following the P5P6
segment in the figure below.
The P(f) function is disabled by default.
Figure 61P(f) Frequency-Watt Function
P The Conext XW Pro output active power in percentage of nominal rated active power
Sn [%Sn].
f - Utility grid frequency in Hz
Parameter
Frequency [Hz] Active Power [%Pn]
Default Range Default Range
Point P1 58 56 to 59 100 0 to 100
Point P2 59.96 59 to 59.96 0 0
Point P3 59.98 59 to 60 0 0
Point P4 60.02 60 to 61 0 0
Table 73PREPA P(f) Frequency-Watt function default and adjustability range
settings
Conext XW Pro Owner's Guide Specifications