into Mandatory Operation (i.e. generates an output current greater than or equal to
80% of pre-disturbance current value).
HFRT
Time [s] Frequency [Hz]
Default Range Default Range
Point P1.H 0.16 N/A 62 60 to 64
Point P2.H 10 0.16 to 10 62 60 to 64
Point P3.H 10 0.16 to 10 61.5 60 to 64
Point P4.H 300 2 to 300 61.5 60 to 64
Point P5.H 300 2 to 300 60.5 60 to 64
Table 76PREPA High Frequency Ride-through (HFRT) default and adjustability range
settings
LFRT
Time [s] Frequency [Hz]
Default Range Default Range
Point P1.L 0.16 N/A 57 56 to 60
Point P2.L 10 0.16 to 10 57 56 to 60
Point P3.L 10 0.16 to 10 57.5 56 to 60
Point P4.L 300 2 to 300 57.5 56 to 60
Point P5.L 300 2 to 300 59.2 56 to 60
Table 77PREPA Low Frequency Ride-through (LFRT) default and adjustability range
settings
Specifications Conext XW Pro Owner's Guide