Conext XW PRO 6848 6,800W 48V Installation
Table Of Contents
- Safety Information
- Label Symbols
- Product Labels
- Radio Frequency Interference Notices
- Audience
- About
- Product Safety Information
- Introduction
- Monitoring Operation
- External Monitoring Control
- Configuration
- Troubleshooting
- Specifications
- Electrical Specifications
- Mechanical Specifications
- Regulatory Approvals
- Grid Support Utility Interactive Functions
- California Rule 21: Smart Inverter Grid-Support Utility Interactive Functions
- Hawaiian Electric Company (HECO) Rule No. 14: Smart Inverter Grid-Support Uti...
- IEEE 1547-2003 Standard for Interconnecting Distributed Resources with Electr...
- Puerto Rico Energy Power Authority (PREPA) Technical Requirements for Interco...
- Defaults
Anti-
Islanding
Reconnect
Time
Grid reconnection time delay at initial start-up or upon disconnection. The
default value for this setting is 300 seconds.
HF
Reconnect
Frequency
The frequency below which the Conext XW Pro will initialize grid
reconnection process. The default value for this setting is 60.5 Hz.
LF
Reconnect
Frequency
The frequency above which the Conext XW Pro will initialize grid
reconnection process. The default value for this setting is 59.3 Hz).
HV
Reconnect
Voltage
The voltage below which the Conext XW Pro will initialize grid reconnection
process. The default value for this setting is 105.83 [%Vn] (percentage of
nominal voltage).
LF
Reconnect
Voltage
The voltage above which the Conext XW Pro will initialize grid reconnection
process. The default value for this setting is 88.33 [%Vn] (percentage of
nominal voltage).
Conext XW Pro Owner's Guide Specifications
182 This document is intended for use by qualified personnel 990-91227A-01