Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Default Settings
This section contains the default configuration settings and ranges for the Conext XW
Pro. Configuration settings can be viewed and changed using the Conext Gateway web
application.
Controls Settings Menu
Item Default Setting Range Step Size
Operating Mode
Standby Standby/Operating n/a
Inverter
Enable/Disable
Enabled Enabled/Disabled n/a
Grid Support Sell
Enable/Disable
Enabled Enabled/Disabled n/a
Charger
Enable/Disable
Enabled Enabled/Disabled n/a
Inverter Settings Menu
Item Default Setting Range Step Size
Low Battery Cut Out
44 V 36–48 V 0.1
LBCO Hysteresis
2 V 0-10 V 0.1
LBCO Delay
10s 0–600s 1
High Battery Cut
Out
65 V 58–70 V 0.1
High SOC Cut Out
99% 0–100% 1
High SOC Cut Out
Delay
60s 0–300s 1
Low Battery Cut Out
SOC
25% 0–100% 1
Low Battery Cut Out
SOC Delay
60s 0–300s 1
Search Mode
Disabled Enabled/Disabled n/a
Search Watts
50 W 25–255 W 5
Search Delay
2s 1–25s 1
Action on
Communication Loss
Heartbeat Disabled
Heartbeat Disabled
Do Nothing
Autonomous Operation
AC Passthrough
n/a
Conext XW Pro Owner's Guide Defaults