Charger Settings Menu
Item Default Setting Range Step Size
Battery Type
Flooded
Flooded, Gel, AGM,
Custom, Li-Ion
n/a
Battery Capacity
440 Ah 0–10000 Ah
a
1
Maximum Charge Rate
100% 5–100% 1
Maximum Bulk Charge
Current
140 A 10–140 A 1
Maximum Absorption
Charge Current
140 A 10–140 A 1
Maximum Float
Charge Current
140 A 10–140 A 1
Charge Cycle
2-Stage
2-Stage, 3-Stage,
External BMS
n/a
Default Batt Temp
Warm Cold, Warm, Hot n/a
Recharge Volts
50 V 40.0–54.0 V 0.1
Absorption Time
180 min 1–480 min 1
Charge Block Start
12:00 AM
12:00 AM–11:59 PM,
00:00–23:59
1
Charge Block Stop
12:00 AM
12:00 AM–11:59 PM,
00:00–23:59
1
Equalize Support
Allowed Allowed/Disallowed n/a
Equalize Voltage
Set Point
64.0 V 54.0–64.0 V 0.1
Bulk/Boost Voltage
Set Point
57.6 V (Flooded)
56.8 V (Gel)
57.2 V (AGM)
40.0–64.0 V 0.1
Absorption Voltage
Set Point
57.6 V (Flooded)
56.8 V (Gel)
57.2 V (AGM)
40.0–64.0 V 0.1
Float Voltage Set
Point
54.0 V (Flooded)
55.2 V (Gel)
53.6 V (AGM)
40.0–64.0 V 0.1
a
Setting the battery capacity to 0 will reset the charging current to its default values. ZeroAh
battery capacity implies there is no absorption exit current criteria and absorption only exits
when the absorption timer (default 3hrs, range 1min-8hr) expires.
Defaults Conext XW Pro Owner's Guide