Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Item
Default Setting Range
Step Size
120
VAC
240
VAC
120
VAC
240
VAC
AC2 Transfer Switch
Delay
36s 10–655s 1
Grid Support Menu
Item Default Range Step Size
Grid Support
Disabled
Enabled/Disabled
n/a
Grid Supp Volts
53.0 V
b
42.0–70.0 V 0.1
Max Sell Amps
c
26 A
0–27 A
1
Load Shave
Disabled
Enabled/Disabled
n/a
Load Shave Amps
48 A 0–48 A 1
Load Shave Start
d
12:00 AM
12:00 AM–11:59 PM,
00:00–23:59
1
Load Shave Stop
12:00 AM
12:00 AM–11:59 PM,
00:00–23:59
1
Sell Block Start
12:00 AM
12:00 AM–11:59 PM,
00:00–23:59
1
Sell Block Stop
12:00 AM
12:00 AM–11:59 PM,
00:00–23:59
1
AC PV Charge SOC
90% 0–100% 1
State of Charge
Control
Disabled
Enabled/Disabled
n/a
Grid Support SOC
Disabled
Enabled/Disabled
n/a
Grid Support SOC
Exit Delay
600s 0–300s 1
EPC Maximum
Discharge Power
6500 W 0–6500 W 1
b
The setting for Grid Supp Volts must be greater or equal to LBCO+2 V. For example, if LBCO is
44 V then the minimum Grid Supp Volts is 46 V.
c
This setting is restricted to the selected external AC1 breaker size.
d
When Load Shaving is enabled, if Load Shave Start and Load Shave Stop are set to the same
time, the Conext XWPro load shaves continuously.
Defaults Conext XW Pro Owner's Guide