Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Generator Support Menu
Setting Default Range Step Size
Generator Support
Enable
Disabled Enabled/Disabled n/a
Generator Support
Amps
48.0 A 0–48.0 A 1
Auxiliary Menu
Item Default Range Step Size
Auxiliary Output
Active Level
Active High Active Low/ Active High n/a
Auxiliary Output
Trigger Source
Low Battery Voltage
Low Battery Voltage
High Battery Voltage
Low Battery
Temperature
High Battery
Temperature
Fault
Bulk Exit
Absorption Exit
Heat Sink
Overtemperature
Battery Low SOC
Time of Day
n/a
Low Battery Trigger
Set
44 V
40.0–58.0 V
0.1
Low Battery Trigger
Set Delay
1.0s 0–600.0s 1
Low Battery Trigger
Clear
48 V
40.0–58.0 V
0.1
Low Battery Trigger
ClearDelay
1.0s 0–600.0s 1
High Battery
Trigger Set
56 V
48.0–70.0 VDC
0.1
High Battery
Trigger Set Delay
1.0s 0–600.0s 1
High Battery
Trigger Clear
52 V
48.0–70.0 V
0.1
Conext XW Pro Owner's Guide Defaults
188 This document is intended for use by qualified personnel 990-91227A-01