Item Default Range Step Size
High Battery
Trigger Clear Delay
1.0s 0–600.0s 1
Low Temperature
Trigger Set
0.0°C -30.0–10.0°C 1
Low Temperature
Trigger Set Delay
1.0s 0–600.0s 1
Low Temperature
Trigger Clear
C -30.0–10.0°C 1
Low Temperature
Trigger Clear Delay
1.0s 0–600.0s 1
High Temperature
Trigger Set
45°C 30.0–60.0°C 1
High Temperature
Trigger Set Delay
1.0s 0–600.0s 1
High Temperature
Trigger Clear
35°C 30.0–60.0°C 1
High Temperature
Trigger Clear Delay
1.0s 0–600.0s 1
Heat Sink High
Temperature Trigger
Set
100°C -30.0–120.0°C 1
Heat Sink High
Temperature Trigger
Set Delay
1.0s 0–600.0s 1
Heat Sink High
Temperature Trigger
Clear
95°C -30.0–120.0°C 1
Heat Sink High
Temperature Trigger
Clear Delay
1.0s 0–600.0s 1
Auxiliary Output
Trigger Block Start
12:00 AM
12:00 AM–11:59 PM,
00:00–23:59
1
Auxiliary Output
Trigger Block End
12:00 AM
12:00 AM–11:59 PM,
00:00–23:59
1
State of Charge
Start
25% 0–100% 1
State of Charge
Stop
90% 0–100% 1