Battery Management Systems Menu
Item Default Range Step Size
Fault on loss of
BMS status
information
Disabled Enabled/Disabled n/a
BMS Status Lost
Fault Trip time
7s 0–200s 1
Charge Voltage
Limit
40.0 V 40.0–72.0 V 0.1
Discharge Voltage
Limit
72.0 V 40.0–72.0 V 0.1
Charge Current
Limit
0 A 0–140.0 A 0.1
Discharge Current
Limit
0 A 0–140.0 A 0.1
Charge Overcurrent
Offset
5.0 A 0–100.0 A 0.1
Charge Overcurrent
Trip Time
2s 0–900s 1
Discharge
Overcurrent Offset
5.0 A 0–100.0 A 0.1
Discharge
Overcurrent Trip
Time
2s 0–900s 1
DC Undervoltage
Offset
3.0 V 0–10.0 V 0.1
DC Undervoltage
Trip Time
10s 0–60s 1
DC Overvoltage
Offset
1.0 V 0–10.0 V 0.1
DC Overvoltage Trip
Time
5s 0–60s 1
Fault on loss of
State of Charge
information
Disabled Enabled/Disabled n/a
Conext XW Pro Owner's Guide Defaults
192 This document is intended for use by qualified personnel 990-91227A-01