Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
WARNING
EQUALIZATION HAZARD
n Only lead acid batteries permitted by the manufacturer should be equalize charged.
Hydrogen and oxygen gases are produced when batteries are equalized and can
potentially cause an explosion if ignited. Corrosive battery acid can escape.
n Provide adequate ventilation and remove all sources of ignition, such as open flames,
sparks, electric motors, relays, light switches, etc.
n Equalization voltage is significantly higher than nominal battery voltage. Detach
electronics that can be damaged by high DC voltage.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
WARNING
BATTERY TYPE AND SETUP HAZARDS
n Incorrect battery configurations or settings for battery types can lead to dangerously
high battery temperature, fire and explosion. To avoid damaging your batteries during
charging or equalization, and to minimize the risk of fire or explosion consult battery
manufacturer's documentation before setting battery parameters and follow the battery
manufacturer's recommended settings.
n Always use and connect the Battery Temperature Sensor (BTS) unless an external BMS
fulfilling this function is used.
n Always verify that the configured battery type matches the battery type being used.
n Custom battery settings should be configured by qualified personnel only.
n When using Lithium-Ion batteries, ensure that the battery pack being used includes a
Battery Management System (BMS) with safety controls. Refer to Li-Ion Battery
Technical Note (document number 990-6359) for additional information.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
In a system where more than one device is capable of equalizing batteries (such as a
system including multiple Conext XW Pro units and/or Conext XW Pro Solar Charge
Controllers), there is no system-wide equalization command for all devices. To
equalize with multiple devices, each would have to be enabled individually.
Alternatively, equalization can be performed using only the selected device. During the
equalization process, one device applies the equalization charge while the other
devices continue to operate in synchronized charge mode, typically in float (three-
stage charging) or no-float (two-stage charging).
LED
The yellow Equalize LED indicates that the Conext XW Pro is equalizing batteries.
Monitoring Operation Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 37