The Conext XW Pro
has begun equalizing
the batteries.
Equalization has been requested but has not
begun. The Conext XW Pro must complete a
charge cycle before applying the equalization
charge.
Using Startup/Shutdown/Standby Modes
Startup/Shutdown control
When the Conext XW Pro is operating, pressing and holding the STARTUP/SHUTDOWN
button (see Figure 10 on page 34) for five seconds shuts down the unit. To return the unit
to its operating state, press the STARTUP/SHUTDOWN button again.
While the Conext XW Pro is turning off, the other inverter information panel buttons stop
working. The shutdown process cannot be cancelled. The Conext XW Pro can only be
restarted once the display is blank.
Standby mode
In Standby mode, the Conext XW Pro stops charging and inverting. Also in Standby
mode, the Conext XW Pro disconnects its internal transfer switches which stops AC to
pass through to the AC output. However, the unit remains powered and present on the
Xanbus network. Lastly, in Standby mode, Conext XW Pro basic and advanced settings
can be changed and put into effect.
To put the Conext XW Pro into Standby mode, press and hold the STARTUP/SHUTDOWN
button and the Equalize button simultaneously for about five seconds. The display shows
Stb. To return the Conext XW Pro to operating mode, press the STARTUP/SHUTDOWN
button momentarily.
Pressing the STARTUP/SHUTDOWN button momentarily while the Conext XW Pro is
operating clears active faults and warnings.
Single-unit installations
In a single-unit installation, when the Conext XW Pro is shut down using the
STARTUP/SHUTDOWN button, Xanbus network power is off. When Xanbus network power
is off, network-connected accessories such as the Automatic Generator Start (Conext
AGS) and Conext Gateway could lose power and stop operating. Conext MPPT solar
charge controllers continue to operate if Xanbus network power is removed, but they do
not continue to communicate with each other.
If the STARTUP/SHUTDOWN button is pressed and held on a Conext XW Pro and a Conext
AGS is installed in the system, the unit stops inverting or charging immediately and shuts
down completely in 120 seconds. During this time, the display shows OFF. This interval
allows the Conext AGS to stop the generator after a cool down period. During the 120
second shutdown time, all network communication is blocked and the unit sends a
shutdown command to all other devices in the system. As well, the inverter information
panel buttons stop working. The shutdown process cannot be canceled. The Conext XW
Pro can only be restarted again once the display is blank.