Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Multiple-unit installations
If the STARTUP/SHUTDOWN power button is pressed and held on a master Conext XW Pro
and a Conext AGS is installed in the system, the unit stops inverting or charging
immediately and turns off completely in 120 seconds. During this time, the display shows
OFF. This interval allows the Conext AGS to stop the generator after a cool down period.
During the 120 second shutdown time, the master unit stops network communication and
the slave units issue an external sync fault (F69) or a system configuration fault (F66). As
well, the inverter information panel buttons stop working. The shutdown process cannot
be cancelled. The Conext XW Pro can only be restarted once the display is blank.
In a multiple-unit installation, when a slave Conext XW Pro is shut down, other Conext
XW Pro units continue to supply Xanbus network power and the Conext AGS and
Conext Gateway continue to operate.
Monitoring Operation Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 39