datapoint in Model 20001. This setting cannot be set in theConext Gateway web
application.
Fallback Action Datapoint Value Description
Heartbeat Disabled 0 (default) Commands revert to default until
communication is re-established. A
warning will not appear.
Do Nothing 1 Continue with the last received set
of control parameters. A warning
will appear.
Autonomous Operation 2 Commands revert to default until
communication is re-established. A
warning will appear.
AC Passthrough 3 3 Conext XW Pro transitions to AC
Passthrough mode. A warning will
appear.
IEEE2030.5
The Conext XW Pro is IEEE2030.5-certified when connected to the Conext Gateway
and External Monitoring & Control is done by client-server communication type. This
includes California Rule Phase 3 Functions 1, 2, 3 and 8:
Phase 3
Function 1
Monitor Key DER Data
n Reactive power (Vars)
n Phase voltage
n Frequency
n Energy storage state of charge (%)
n Operational state
Phase 3
Function 2
DER Disconnect and Reconnect Command
Phase 3
Function 3
Limit Maximum Active Power Mode
Phase 3
Function 8
Scheduling Power Values and Modes
n Volt-Var curve control
n Fixed power factor control
n Volt-Watt curve control
External Monitoring Control Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 49