Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Grid Support Sell
Enable/Disable
Enables or disables grid-interactive Conext XW Pro
features, such as grid support and grid sell mode.
Unless an external BMS is utilized and Charge Cycle is
set accordingly, to allow grid support to function after
battery charging has completed, it is recommended to
set the Charge Cycle to 2- Stage. The MPPT
controllers must still be set to 3-stage. When using load
shave, turning ON Sell and setting Maximum Sell
Amps to 0.0 is a way to make the net power flow to the
grid zero. If sell is not enabled, there will be a net
purchase of as much as 2.0 - 3.0 kWh per day due to the
current control loop not allowing any outgoing current. If
you wish to further reduce grid draw using this function,
enable sell mode even if you do not wish to export
power and set Maximum Sell Amps to a value of 0.
Charger Enable/Disable
Enable or disable the charger.
Force Charger State
Manually changes the charge stage to either bulk or float
(when 3- Stage cycle is selected), bulk or no float (when
2-Stage cycle is selected), or Constant Voltage and
Current. (when Lithium Ion is selected)
This command has no effect if load shaving is enabled.
For more information, see "Load Shaving" in Table 2 on
page 42.
Manual Aux
Sets the state of the auxiliary output. ManualOn or
ManualOff allow manual control of the auxiliary output.
When set to Automatic, a trigger source can then be
selected.
For default settings, see "Controls Settings Menu" on page184.
Inverter Settings
The Inverter Settings menu contains settings that control when the Conext XW
Pro starts and stops producing AC output.
Item Description
Low Battery Cut
Out
Low Battery Cut Out (LBCO) controls when the inverter stops
producing AC output due to a low battery voltage condition. The
inverter will stop producing AC output only after this level has been
reached for the period of time set by the Low Battery Cut Out
Delay. This setting is not temperature compensated.
Table 5Inverter Settings Menu
Configuration Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 55