Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Item Description
Search Delay
Search Delay sets the time between search pulses. When
searching for loads, the Conext XW Pro sends out search pulses
on AC OUT to determine the presence of a load above Search
Watts. Conext XW Pro power draw while in search mode
decreases when Search Delay is increased, but the Conext XW
Pro response time to active loads is slower.
High SOC Cut Out
The upper limit of whereConext XW Pro will charge its connected
battery pack when State of Charge Control is enabled.
When the battery pack has been charged at or above this level
after a delay set in High SOC Cut Out Delay, charging will
terminate.
High SOC Cut Out
Delay
The time duration for which the battery State of Charge must be at
or above High SOC Cut Out before terminating.
Low Battery Cut
Out SOC
The lower limit of where Conext XW Pro will discharge its
connected battery pack when State of Charge Control is
enabled. When the battery pack has been discharge at or below
this level after a delay set in Low Battery Cut Out SOC Delay,
the discharging activity will terminate.
Low Battery Cut
Out SOC Delay
The time duration for which the battery State of Charge must
be at or below Low Battery Cut Out SOC before terminating the
discharge.
Action on
Communication
Loss
Configures the action taken during a general communications loss
with the Conext Gateway.
For default settings, see "Inverter Settings Menu" on page184.
Using the Low Battery Cut Out and LBCO Delay Settings
WARNING
ADVANCED CONFIGURATION HAZARD
n Advanced menu settings should be used by qualified personnel only.
n Three phase operation should be configured by qualified personnel only.
n Consult with the local utility before enabling Conext XW Pro sell mode or grid support
functions.
n Do not change these settings unless you are under the supervision and direction of
qualified personnel.
n Connect the Conext Gateway and the network router connected to the Conext Gateway
to an assured power source during configuration.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Configuration Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 57