WARNING
BATTERY TYPE AND SETUP HAZARDS
n Incorrect battery configurations or settings for battery types can lead to dangerously
high battery temperature, fire and explosion. To avoid damaging your batteries during
charging or equalization, and to minimize the risk of fire or explosion consult battery
manufacturer's documentation before setting battery parameters and follow the battery
manufacturer's recommended settings.
n Always use and connect the Battery Temperature Sensor (BTS), unless an external
BMS fulfilling this function is installed.
n Always verify that the configured battery type matches the battery type being used.
n Custom battery settings should be configured by qualified personnel only.
n When using Lithium-Ion batteries, ensure that the battery pack being used includes a
certified Battery Management System (BMS) with safety controls. Refer to Li-Ion Battery
Technical Note (document number 990-6359) for additional information.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
The Charger Settings menu provides options for configuring the Conext XW Pro to
operate from your battery bank.
Item Description
Batt Type
Sets the system battery chemistry and type: Flooded (default), AGM,
Gel, Lithium Ion, and Custom.
Battery Bank
Capacity
Selects the system battery capacity in Ah (amphours). Setting the
Battery Bank Capacity to 0 resets the charging current to its
default values. Zero Ah battery capacity implies there is no
absorption exit current criteria and absorption only exits when the
absorption timer (default 3 hours, range 1 minute-8 hours) expires.
Maximum Charge
Rate
Sets the percentage of the maximum DC output current that is
available to the charger. The maximum DC output current for
different models is:
n XW Pro 6848 NA—140 A
If multiple Conext XW Pros are charging the same battery bank, set
each inverter's Maximum Charge Rate to 1/n of the desired charge
rate (where n is the number of inverter/chargers).
Always refer to the battery manufacturer’s specifications before
setting the Maximum Charge Rate. Do not set the Maximum
Charge Rate above these specifications.
Table 6Charger Settings Menu
Conext XW Pro Owner's Guide Configuration
60 This document is intended for use by qualified personnel 990-91227A-01