Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Item Description
Maximum Bulk
Charge Current
Adjustable only when the Batt Type is set to Li-Ion. Sets the bulk
current for a lithium ion battery type. This configures the current limit
when the Conext XW Pro is in Bulk Charge Mode. However,
between the maximum charge current (Maximum Charge Rate ×
maximum DC output current) and the value set here, the Conext XW
Pro charger will charge at the lesser of these two values.
Maximum
Absorption Charge
Current
Adjustable only when the Batt Type is set to Li-Ion. Sets the
absorb current for a lithium ion battery type. This configures the
current limit when the Conext XW Pro is in Absorption Charge
Mode. However, between the maximum charge current (Maximum
Charge Rate × maximum DC output current) and the value set
here, the Conext XW Pro charger will charge at the lesser of these
two values.
Maximum Float
Charge Current
Adjustable only when the Batt Type is set to Li-Ion. Sets the float
current for a lithium ion battery type. This configures the current limit
when the Conext XW Pro is in Float Charge Mode. However,
between the maximum charge current (Maximum Charge Rate ×
maximum DC output current) and the value set here, the Conext XW
Pro charger will charge at the lesser of these two values.
Charge Cycle
Sets the charging method: 3-Stage (bulk, absorption, float), 2-
Stage (bulk,absorption, no float), or External BMS.
Default Battery
Temperature
Selects the battery temperature charging compensation if a battery
temperature sensor is not installed. In the absence of a battery
temperature sensor, the charger uses one of three settings: Cool
(5°C/41 °F), Warm (25 °C/77 °F), or Hot (40 °C/104 °F).
Recharge Voltage
When charger is set for 2-stage operation, sets the battery voltage
level at which a new charge cycle begins. Recharge Voltage is
automatically temperature compensated to be consistent with the
charge voltage (also temperature compensated).
Absorption Time
Sets the maximum time spent in the absorption stage, before
transitioning to float or no float.
Charge Block
Start
Sets the time to halt charging on AC1 (Grid). The AC2 (Gen) port is
unaffected by the Conext XW Pro block settings. The charger block
start and stop settings allow you to select when the charger stops
charging on AC1. To disable the charger block function, set Charge
Block Start and Charge Block Stop to the same time.
Charge Block Stop
Sets the time that charging on AC1 can resume. At the Charge
Block Stop time, charging on AC1 is enabled again.
Equalize Support
Enables or disables the ability to enter an equalization cycle. Refer
to the battery manufacturer’s specifications to determine whether
equalization is recommended.
Configuration Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 61