Equalization Procedure
To start equalizing the batteries, do one of the following:
1. On the Charger Settings menu, toggle the Equalize Now toggle switch to
Enabled.
2. Press the Equalize button on the inverter information panel for five seconds.
If the Conext XW Pro will not perform the equalization, seeWarning W96 Cannot
Equalize” in Table 23 on page 110.
WARNING
EQUALIZATION HAZARD
Only flooded lead acid batteries should be equalize charged. Hydrogen and oxygen gases
are produced when batteries are equalized and can potentially cause an explosion if
ignited. Corrosive battery acid can escape.
n Provide adequate ventilation and remove all sources of ignition, such as open flames,
sparks, electric motors, relays, light switches, etc.
n Equalization voltage is significantly higher than nominal battery voltage. Detach
electronics that can be damaged by high DC voltage.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
NOTE: In a system where more than one device is capable of equalizing batteries (such
as a system including multiple Conext XW Pro units and Conext MPPT solar charge
controllers, there is no system-wide equalization command for all devices. To equalize
with multiple devices, each would have to be enabled individually. Alternatively,
equalization can be performed using only one device. During the equalization process,
one device applies the equalization charge while the other devices continue to operate in
synchronized charge mode, typically in float (three-stage charging) or no-float (two-stage
charging).
Conext XW Pro Owner's Guide Configuration
72 This document is intended for use by qualified personnel 990-91227A-01