WARNING
ADVANCED CONFIGURATION HAZARD
n Advanced menu settings should be used by qualified personnel only.
n Three phase operation should be configured by qualified personnel only.
n Consult with the local utility before enabling Conext XW Pro sell mode or grid support
functions.
n Do not change these settings unless you are under the supervision and direction of
qualified personnel.
n Connect the Conext Gateway and the network router connected to the Conext Gateway
to an assured power source during configuration.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
The AC Settings menu configures the voltage and frequency limits for ACport1 (Grid)
and AC port 2 (Gen). These are the limits at which the Conext XW Pro considers AC
input voltage qualified—that is, suitable for charging batteries or passing through to loads
attached to AC OUT. If the input voltage is not qualified according to these settings, the
Conext XW Pro reverts to inverting external DC energy to AC energy for loads on AC
OUT.
Item Description
AC Priority
Sets the priority for the AC input source (AC1 or AC2) for
qualification and transfer.
In systems that use both utility grid (AC1) and generator (AC2) input,
it is recommended that you set AC Priority to AC1. Assuming the
generator is intended for occasional use only, the Conext XW Pro
will use utility power. It will use the generator only if AC1 is
unavailable, and if the generator is running.
AC1 Breaker
Sets the AC1 (Grid) breaker size, based on the size of the breaker
installed upstream from the AC1 connection port. Theinstalled
breaker size must not exceed the capacity of the upstream
distribution panel. The Conext XW Pro helps to limit the maximum
current draw on AC1 by derating its charging current to an
equivalent of 80% of the AC1 breaker setting.
However, if the connected loads on AC OUT exceed the AC1
breaker setting, the upstream AC breaker trips. The breaker may not
trip if grid support is enabled and battery voltage is above the Grid
Support Voltage setting, or if peak load shave is enabled and the
load shave time window is active.
Table 7AC Settings Menu
Configuration Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 73