Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Generator Support Amps is set to 48A, the inverter will only start to assist the
generator at a current level which would measure approximately 49A which is 1A higher
than the Generator Support Amps value.
For default settings, see Generator Support Menu on page 188.
AGS Setting in a Multi-Unit System
To prevent the generator from nuisance cycling when the multi-unit Conext XW Pro units
are installed with an external contactor (that is, the generator starts and stops in a loop)
set Inverter Load Start/Stop Triggers to Disabled under the AGS device
Configuration menu in the Conext Gateway web application.
Auxiliary Output Settings
WARNING
ADVANCED CONFIGURATION HAZARD
n Advanced menu settings should be used by qualified personnel only.
n Three phase operation should be configured by qualified personnel only.
n Consult with the local utility before enabling Conext XW Pro sell mode or grid support
functions.
n Do not change these settings unless you are under the supervision and direction of
qualified personnel.
n Connect the Conext Gateway and the network router connected to the Conext Gateway
to an assured power source during configuration.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
The Aux menu allows you to enable and set the auxiliary output. Theauxiliary output
provides 12 volts DC at 250 milliamps to power a relay, indicator light, or alarm.
NOTE: Changing Auxiliary Output Trigger Level resets the auxiliary output.
If an auxiliary output trigger is active, changing the trigger level will clear the trigger.
For default settings, see "Auxiliary Menu" on page188.
Setting Description
Auxiliary Output
Active Level
Sets the mode (polarity) of the auxiliary output. When triggered,
the output can be active high (12 V output turns on) or active
low (output is high until the trigger turns it off).
Auxiliary Output
Trigger Source
Selects the desired condition (trigger source) to activate the
auxiliary output.
Table 10Auxiliary Menu Values
The following parameter set controls the activation and de-activation conditions for the
Auxiliary Output and are available for each trigger source.
Conext XW Pro Owner's Guide Configuration
80 This document is intended for use by qualified personnel 990-91227A-01