Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Setting Description
Trigger Set
Sets the voltage or temperature level (depending on the
selected trigger source) at which the auxiliary output is
activated. If the selected Trigger Source is a battery voltage,
the range also varies according to the nominal battery voltage
of your system.
Trigger Set
Delay
Sets a delay period between when the trigger occurs and when
the auxiliary output is activated.
Trigger Clear
Sets the voltage or temperature level (depending on the
selected trigger source) at which the auxiliary output becomes
inactive.
Trigger Clear
Delay
Sets a delay period between when the Trigger Clear setting
occurs and when the auxiliary output becomes inactive.
Table 11Auxiliary Menu Values
Trigger Source Descriptions
Low Battery
Voltage
Activates the auxiliary output when the battery voltage falls
below Low Battery Voltage after the trigger delay time. The
auxiliary output turns off when the battery voltage rises above
the clear setting after the Clear Delay time. Use this setting if
the auxiliary output needs to control a relay to disconnect loads
from a battery or to activate a low battery voltage alarm such as
a buzzer or light.
High Battery
Voltage
Activates the auxiliary output when the battery voltage rises
above High Battery Voltage for the trigger delay time. The
auxiliary output turns off when the battery voltage falls below
the clear setting for the Clear Delay time. This setting is
useful for:
n Installations that have another external charging source
such as a wind generator or hydro generator connected
directly to the batteries. The Conext XW Pro auxiliary output
can control a relay to disconnect the external charging
source from the battery or control a relay to turn on a
diversion load.
n Activating a high battery voltage alarm such as a buzzer or
light.
n Activating a vent fan to ventilate the battery compartment.
Table 12Trigger Source Descriptions
Configuration Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 81