Low Battery
Temperature
Activates the auxiliary output when the battery temperature falls
below Low Battery Temperature for the trigger delay time.
The auxiliary output turns off when the battery temperature
rises above the clear setting for the Clear Delay time. Battery
temperature is measured with a battery temperature sensor. Do
not use this setting if a battery temperature sensor is not
installed.
High Battery
Temperature
Activates the auxiliary output when the battery temperature
rises above High Battery Temperature for the trigger delay
time. The auxiliary output turns off when the battery
temperature falls below the clear setting for the Clear Delay
time. Battery temperature is measured with a battery
temperature sensor. Do not use this setting if a battery
temperature sensor is not installed. With this setting, the
auxiliary output can turn on a fan to vent the battery
compartment.
Heat Sink
Overtemperature
Activates the auxiliary output when the heat sink temperature
exceeds its trigger set for longer than its set delay. The
auxiliary output turns off when the temperature falls below its
clear threshold for longer than its clear delay.
Bulk Exit
Exits charge bulk mode. In charge bulk mode, the Conext XW
Pro operates as a constant power source to the battery bank.
The aux port clears its state when the inverter exits from Bulk
charge stage.
Absorption Exit
Exits charge absorption mode and starts the following mode,
depending on whether the unit is set to two or three-stage
charge. The aux port clears its state when the inverter exits
from Absorption charge stage.
Fault
Activates the auxiliary output when a fault occurs. The auxiliary
output clears when the fault is cleared.
Battery Low
State of Charge
This feature works in conjunction with the Conext Battery
Monitor or an external BMS. This auxiliary output is triggered
when the state of charge falls outside of the range of 25-90% of
total battery charge.
Time of Day
When Time of Day is selected as a trigger source, the
Trigger Block Start and Block End become available.
Both can be set to a value between 12:00 AM and 11:59 PM.
Block Start is when the Auxiliary Output goes into inactive
state. Block End is when the Auxiliary Output goes into active
state.