Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Associations Settings
WARNING
ADVANCED CONFIGURATION HAZARD
n Advanced menu settings should be used by qualified personnel only.
n Three phase operation should be configured by qualified personnel only.
n Consult with the local utility before enabling Conext XW Pro sell mode or grid support
functions.
n Do not change these settings unless you are under the supervision and direction of
qualified personnel.
n Connect the Conext Gateway and the network router connected to the Conext Gateway
to an assured power source during configuration.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
The Associations menu contains additional settings to allow the Conext XW Pro to
function as part of a multi-unit networked system.
Setting the connections for a Xanbus-enabled device provides a way of identifying non-
network associations for Xanbus-enabled devices and enhancing networked power
system management. When connections are set, devices of different types become
associated and can share sources, e.g. a common DC input source, or a common
grid/generator source.
In multi-unit networked systems, multiple inverter/chargers can be stacked to produce
increased charge current. To achieve this functionality, the devices must be configured
to the same DC connection, such as House Battery Bank 1. The units will collaborate on
battery charging by communicating with other units on this shared DC connection.
NOTE: When configuring clusters of three Conext XW Pro units (or a grouping of up to
six in a grid-tie application), each clusters DC connections must be set to the same
battery bank. If one of the units is set with a different DC connection, a system
configuration fault (F66) occurs.
Item Description
Battery
Association
DC input and output connection. This is the common DC connection
shared between the Conext XW Pro, charge controllers, and
referenced by the Conext AGS.
Table 14Associations Menu
Configuration Conext XW Pro Owner's Guide