Conext XW PRO 6848 6,800W 48V Installation
Table Of Contents
- Safety Information
- Label Symbols
- Product Labels
- Radio Frequency Interference Notices
- Audience
- About
- Product Safety Information
- Introduction
- Monitoring Operation
- External Monitoring Control
- Configuration
- Troubleshooting
- Specifications
- Electrical Specifications
- Mechanical Specifications
- Regulatory Approvals
- Grid Support Utility Interactive Functions
- California Rule 21: Smart Inverter Grid-Support Utility Interactive Functions
- Hawaiian Electric Company (HECO) Rule No. 14: Smart Inverter Grid-Support Uti...
- IEEE 1547-2003 Standard for Interconnecting Distributed Resources with Electr...
- Puerto Rico Energy Power Authority (PREPA) Technical Requirements for Interco...
- Defaults
Advanced Features
WARNING
ADVANCED CONFIGURATION HAZARD
n Advanced menu settings should be used by qualified personnel only.
n Three phase operation should be configured by qualified personnel only.
n Consult with the local utility before enabling Conext XW Pro sell mode or grid support
functions.
n Do not change these settings unless you are under the supervision and direction of
qualified personnel.
n Connect the Conext Gateway and the network router connected to the Conext Gateway
to an assured power source during configuration.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Item Description
Remote Power Off
Enables or disables the Remote Power Off function. Enable
this setting if an external switch has been connected to the
Conext XW Pro auxiliary port. Seethe Conext XW Pro
Installation Guide for more information about the auxiliary port.
Power Save
When enabled, power save mode can reduce tare loss from the
battery by reducing output from 240volts to 220 volts when the
loads are less than 100 watts. When the Conext XW Pro detects
loads higher than 100watts, it produces the full 240 volts.
Power Save mode is disabled bydefault.
Sell Delay 40
Sec
When enabled—and other conditions are satisfied—there will
be a 40 second delay before the system starts exporting energy
to the grid. When disabled, the default value of 20 seconds is
used. This feature is useful when the battery voltage is not
constant. It also helps avoid power fluctuations during sell.
As an exception, there will be zero time delay when the battery
voltage suddenly rises to 2V above Grid Support Voltage.
Forexample, a wind turbine or micro hydro connected to a
small battery bank may create a sudden change on the battery
voltage. In this case the system will immediately respond to
convert the energy from the battery to grid.
Table 15Advanced Features Menu
Configuration Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 87