Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Item Description
Fault on
loss of BMS
status
information
Configures the Conext XW Pro response to lost BMS Status message from
the Conext Gateway. Set to Enabled to configure the Conext XW Pro to
activate Fault F90 and go offline, and to Disabled to configure it to activate
Warning W90 and use measured battery voltage for control until
communications of BMS status information is restored..
BMS Status
Lost Fault
Trip time
The time delay from the moment the BMS Status message from the Conext
Gateway is lost to the Conext XW Pro activating W90 if Fault on loss of
BMS status information is disabled, or F90 if enabled.
Charge
Voltage
Limit (BMS
status lost)
The default charge voltage limit applied when the value normally provided
by the associated Battery Management System is no longer being
received.
Discharge
Voltage
Limit (BMS
status lost)
The default discharge voltage limit applied when the value normally
provided by the associated Battery Management System is no longer
being received.
Charge
Current
Limit (BMS
status lost)
The default charge current limit applied when the value normally provided
by the associated Battery Management System is no longer being
received.
Discharge
Current
Limit (BMS
status lost)
The default discharge current limit applied when the value normally
provided by the associated Battery Management System is no longer
being received.
Charge
Overcurrent
Offset
Offset added to the charge overcurrent limit broadcasted by the associated
BMS. The resulting threshold becomes the Conext XW Pro’s own charge
overcurrent limit.
Charge
Overcurrent
Trip Time
The time delay from the moment charge current exceeds the threshold
determined above until the Conext XW Pro activates fault F73.
Discharge
Overcurrent
Offset
Offset added to the discharge overcurrent limit broadcasted by the
associated BMS. The resulting threshold becomes the Conext XW Pro’s
own discharge overcurrent limit.
Discharge
Overcurrent
Trip Time
The time delay from the moment discharge current exceeds the threshold
determined above until the Conext XW Pro activates fault F71.
DC
Undervoltage
Offset
Offset added to the undervoltage limit broadcasted by the associated
BMS. The resulting threshold becomes the Conext XW Pro’s own
undervoltage limit.
Table 17ξ˜ƒBattery Management System Menu
Conext XW Pro Owner's Guide Configuration
90 This document is intended for use by qualified personnel 990-91227A-01