Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
DC
Undervoltage
Trip Time
The time delay from the moment battery voltage exceeds the threshold
determined above until the Conext XW Pro activates fault F74.
DC
Overvoltage
Offset
Offset added to the overvoltage limit broadcasted by the associated BMS.
The resulting threshold becomes the Conext XW Pros own overvoltage
limit.
DC
Overvoltage
Trip Time
The time delay from the moment battery voltage exceeds the threshold
determined above until the Conext XW Pro activates fault F75.
Fault on
loss of
State of
Charge
information
Configures the Conext XW Pro response to lost BMS State of Charge from
theConext Gateway. Set to Enabled to configure the Conext XW Pro to go
offline, and to Disabled to configure it to use measured battery voltage for
control.
For default settings, see "Battery Management Systems Menu" on page192.
Device Instance Settings
WARNING
ADVANCED CONFIGURATION HAZARD
n Advanced menu settings should be used by qualified personnel only.
n Three phase operation should be configured by qualified personnel only.
n Consult with the local utility before enabling Conext XW Pro sell mode or grid support
functions.
n Do not change these settings unless you are under the supervision and direction of
qualified personnel.
n Connect the Conext Gateway and the network router connected to the Conext Gateway
to an assured power source during configuration.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Item Description
Device Number
Allows setting of a unique unit number in a multiple-unit system.
In multi-unit configurations, the Conext XW Pro designated as
the Master must be assigned the Device Number of 1.
Device Name
Allows customization of the default device name. This setting is
optional and does not affect operation.
System Instance
Identifies the Xanbus association of all devices on the same
network. Accepts numerical values only.
Table 18Device Instance Menu
For default settings, see "Device Instance Menu" on page193.
Configuration Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 91