When using the system for time-of-use metering, the system should be designed with a
battery capacity large enough to support loads during the entire peak rate period without
reaching the Low Battery Cut Out or Low Battery Cut Out SoC setting.
NOTE: If the batteries reach the Low Battery Cut Out setting, the Conext XW Pro
automatically reconnects to the utility grid to maintain the connected load.
Self-Consumption
PLS can also be used with time-of-use metering to support self-consumption. In the self-
consumption mode of operation, the Conext XW Pro delays Peak Load Shave mode by a
fixed time of 2 hours. This is done by allowing a priority for the MPPT solar charge
controller to charge the battery bank.
This configuration can be selected under the Conext XW Pro menu by setting Peak
Load Shaving Delayunder Advanced Features to Enabled. The default setting for
is Disabled.
Managing Firmware
The firmware running on the Conext XW Pro can be upgraded under the Firmware tab
in theConext XW Pro menus. A single firmware binary file can be pushed to all networked
Conext XW Pros by loading the file and selecting Upgrade All XWs. Firmware can
be downloaded from https://solar.schneider-electric.com/.
Figure 24Upgrading Firmware
Conext XW Pro Owner's Guide Configuration