Installation Manual

Installation
1–22 975-0639-01-01 Rev D
This guide for use by qualified personnel only
Figure 1-11 Conext SW AC INPUT and OUTPUT Connections
L1
L2
N
AC Cable
(3)
(4)
side AC
knockouts
bottom AC
knockouts
to Inverter
AC INPUT
strip at least
2” (50mm)
strip at least
1/2” (13mm)
Inverter Load Panel
AC Source
Main Panel
(9)
(1)
(2)
Transfer switch
(1) Make the wiring connections to the AC
source main panel.
(2) Route the AC cable to the inverter/
charger.
(3) Remove the wiring compartment cover
panel on the inverter/charger.
(4) Remove the AC knockouts from the side
or bottom (or both). Do not leave the
knockout inside the wiring compartment.
(5) Install strain-relief clamps in the AC
knockouts.
(6) Route the AC input cable through the AC
input knockouts and inside the wiring
compartment.
(7) Connect Lines 1 & 2 to L1 & L2, Neutral
to N, ground to on the AC input terminals.
If solid ground wire is being used, the wire
can be connected directly under the screw
heads. If stranded ground wire is being
used, ring terminals must be used.
(8) Tighten the terminal screws. Leave a
service loop in the wires inside the wiring
box.
(9) Route the AC output cable through the
AC output knockouts and inside the wiring
compartment.
(10) Connect Lines 1 & 2 to
L1 & L2, Neutral to N,
ground to on the AC
output terminals. If solid
ground wire is being used,
the wire can be connected
directly under the screw
heads. If stranded ground
wire is being used, ring
terminals must be used.
(11) Tighten the terminal
screws. Leave a service
loop in the wires inside the
wiring box.
(12) Make the wiring
connections to the inverter
load panel.
(13) Replace the wiring
compartment cover panel
on the inverter/charger.