Inverter/Charger Installation
975-0639-01-01 Rev D 1–25
This guide for use by qualified personnel only
Connecting the DC Cables to the DC Switchgear
WARNING
FIRE HAZARD
Use only appropriately sized copper cable. Loose connections, improper
connections, and under-rated cables will overheat.
Make sure the supplied nuts on the inverter/charger are tightened to a
torque of 10–11 ft-lbs (13.5–14.9 Nm). Torque all other connections to the
manufacturer’s specifications.
Make sure the DC cables, washers, and nuts are assembled in the order
shown in Terminal Connection in Figure 1-13 on page 1–26.
Failure to follow these instructions can result in death or serious injury.
NOTICE
REVERSE POLARITY DAMAGE
Check cable polarity at both the battery and the inverter/charger before
making the final DC connection or closing the DC breaker or disconnect.
Positive (+) must be connected to positive (+). Negative (–) must be
connected to negative (–).
Failure to follow these instructions can damage the inverter/charger.