Installation Manual

Inverter/Charger Installation
975-0639-01-01 Rev D 1–27
This guide for use by qualified personnel only
Step 5: Connecting the BTS and Xanbus-enabled Components
Battery
Temperature
Sensor (BTS)
Installing a BTS extends the life of a battery by preventing overcharging in warm
temperatures and undercharging in cold temperatures. With a BTS monitoring
the battery temperature, the voltage delivered to the battery is adjusted
according to the battery’s actual temperature.
The BTS has a self-adhesive backing and attaches to the side of the battery. The
BTS also comes with a metal tab. A 25-ft (7.6-m) cable is supplied with the BTS.
Xanbus-enabled
Components
These include the SCP, the AGS, Conext ComBox, and a solar charge controller.
The order in which the components are connected to the inverter/charger does
not matter. The most important aspect of the installation of these components is
the attachment of network terminators at each end of the network.
WARNING
ELECTRICAL SHOCK HAZARD
Connect and disconnect DC wiring only after opening and locking out the
disconnect switches or breakers at all AC and DC sources.
Failure to follow these instructions can result in death or serious injury.
ConextSW-NA-InstallationGuide.book Page 27 Tuesday, July 21, 2015 4:39 PM