Installation Manual

Installation
1–40 975-0639-01-01 Rev D
This guide for use by qualified personnel only
Restrictions on Motor Size
An appliance may require three to six times its normal running current in order to
start. The Conext SW can handle surges up to twice its rated amount (surge
current) for five seconds. For example, the model Conext SW 4024 120/240 is
rated as having a maximum continuous output current of 15 amps
and a surge
capability of 32 amps. In motors, the locked rotor amp (also called its starting
current) may be specified on the motor nameplate as “LRA” or “LRI”. The LRA
must not exceed the surge current rating of 32 amps.
When considering appliances with large motors, follow these guidelines:
Make sure that the motor’s LRA rating is no more than surge current amps.
The Conext SW may not be able to start a motor with a higher LRA, and the
Conext SW will shut down if the attempt is made.
Make sure the battery bank, DC cables and DC fuses are capable of
handling up to 600 amps DC for five seconds. A weaker circuit may not be
able to provide sufficient power to the Conext SW to allow the Conext SW to
start up the appliance. Again, if the circuit cannot deliver the required
current, the system may shut down or the fuse may open.
Table 1-5 Battery Sizing Worksheet
Appliance
(A) Power
Consumption (Watts)
(B) Operating Time per
Day (Hours)
Daily watt-hours
needed for this
appliance
(= A × B)
W hours Wh
W hours Wh
W hours Wh
W hours Wh
W hours Wh
W hours Wh
W hours Wh
W hours Wh
Total daily watt-hours of AC load Wh
× Number of days between charges
= Total watt-hours of AC load between charges Wh
Battery Ah used between charges (divide by 20 for 24 volt system) Ah
Recommended Battery Bank Size in Ah (multiply by 2) Ah
ConextSW-NA-InstallationGuide.book Page 40 Tuesday, July 21, 2015 4:39 PM