Conext SW4048 4,000W 48V Installation

Table Of Contents
Troubleshooting
5–2 975-0638-01-03
General Troubleshooting Guidelines
This section will help you narrow down the source of any problem you may
encounter. Please read the following troubleshooting steps:
1. Check for a warning or fault detection message on the SCP or a fault code on
the inverter information panel. If a message is displayed, record it
immediately.
2. As soon as possible, record the conditions at the time the problem occurred.
These details should include the following as well as any other information
asked for on the page. These details are:
Firmware revision of the Conext SW
Type of loads the Conext SW was running or attempting to run
Battery condition at the time of fault detection (battery voltage or
temperature, for example), if known
Recent sequence of events (for example, charging had just finished, AC
generator had stopped but the inverter did not come on)
Any known unusual AC input factors such as low voltage or unstable
generator output
Extreme conditions which may have existed at the time (temperature or
moisture, for example)
3. Attempt the solution indicated in these guidelines.
4. If your inverter front panel or SCP is not displaying a Fault detection light,
check the following list to make sure that the present state of the installation
allows proper operation of the unit. Read these guidelines carefully.
p Is the Conext SW located in a clean, dry, adequately ventilated area?
p Have the AC input breakers opened? If so, your pass-through load may have
exceeded the rating of one or more of the input breakers.
p Are the battery cables adequately sized and short enough? See the
Installation Guide for more information.
p Is the battery in good condition and are all DC connections tight?
p Are the AC input and output connections and wiring in good condition?
p Are the configuration settings correct for your particular installation?
p Are the display panel and the communications cable properly connected
and undamaged?
p Is the battery temperature sensor and its cable properly connected and
undamaged?
5. Contact Customer Service for further assistance. Please be prepared to
describe details of your system installation and provide the model and serial
number of the unit. See the front and/or back of the manual for contact
information.