Troubleshooting
5–10 975-0638-01-03
F67
Watchdog error Manual Unit’s control
board may be
damaged.
Service required.
F68
Transformer Over
Temperature
Automatic Same as F57. Same as F57.
F69
External Sync
Failed
Escalating A non-Xanbus
device may be
connected to the
Xanbus ports.
Connect only Xanbus-
enabled devices to the
Xanbus ports.
F73
Transformer Temp
unreadable
Automatic Temperature
sensor is
damaged.
Service required.
F79
Battery Sensor
Short
Automatic The BTS has been
damaged.
Replace the BTS.
F85
PowerBoard Over
Temperature
Automatic Same as F57. Same as F57.
F86
Dead Battery
Detected
Automatic When only Line 1 is
qualified and
battery voltage is
below the
allowable charging
voltage.
Both Line 1 and Line 2 must
qualify to charge the battery.
Recharge the battery with an
external charging device.
If the error persists, then the
battery may be defective.
Replace the battery.
F88
MPPT Ground
Fault
Automatic In a Xanbus
network, an MPPT
has detected a
ground fault (MPPT
generated code
F56).
Check the MPPT and clear
the ground fault.
F89
Battery
Discharge Over
Current
Escalating There is an
excessive load on
the Li-ion battery.
This fault applies
only to Li-ion
batteries.
Change the default threshold
of the max battery discharge
current limit or reduce the
load.
F90
External BMS
Disconnected
Automatic Communication
has been lost with
the Battery
Management
System of the Li-
ion battery.
Check the Xanbus network
connections to the Li-ion
battery. Contact the battery
manufacturer if a connection
problem cannot be found.
Table 5-3 Fault Detection Messages
Code Message Type Cause Solution