Conext SW4048 4,000W 48V Installation
Table Of Contents
- Conext™ SW Inverter/Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-03 Revision: Date: 5-2020
- Contact Information solar.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Safety Information
- Precautions When Working With Batteries
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Basic Protection Features
- Grid-interactive and Other Features
- Load Shaving
- AC Support
- Grid-Interactive Delay Feature
- AC Coupling
- AC Couple Smart Charge
- Storing the State of the Inverter Mode
- NoLoadVD
- Low Battery Cut Out Hysteresis
- LBCO Delay
- Lithium Ion Battery Type
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- AC Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Advanced Features Menu
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Troubleshooting the Conext SW via the SCP
975-0638-01-03 5–11
Table 5-4 provides a detailed description of the warning messages and solutions.
If you are unable to resolve the problem after referring to this table, contact
customer service.
Table 5-4 Warning Messages
Code Message Fault Type Cause Solution
W48
DC under voltage
(Warning)
Automatic Voltage at the DC
input terminals is
below the Low
Battery Cut Out
(LBCO) setting.
Check for the correct battery
voltage at the inverter's DC
input terminals.
Check for external DC loads
on the batteries.
Check condition of batteries
and recharge if necessary.
Reduce the Low Battery Cut
Out (LBCO) setting.
Battery bank capacity may
be inadequate for the loads
in the system.
W92
Input Connected
to 3-Phase AC
Automatic
(Appears only in
split-phase model
units)
A 3-Phase cable is
connected to the
AC IN L1/L2/N
terminals.
Disconnect the AC input
power source immediately
and remove the cable from
the inverter’s AC IN terminals.
Service may be required.
W93
Wrong Batt
Temperature
Sensor
Automatic An unknowns BTS
was plugged into
the BTS port.
Use only the BTS that was
provided with the Conext SW
Inverter/Charger. To order,
use product number 808-
0232-02.
NOTE: A W252 event code is reported by the SCP when restoring Conext SW to
its default settings. See page 4–35. A W298 event code is reported by the SCP
when the AC output frequency is changed. See also page 4–35. These events
will clear automatically.