Configuring Basic Settings
975-0638-01-03 4–7
Configuring Basic Settings
An overview of the Conext SW Basic Settings menu structure is shown below.
NOTICE
EQUIPMENT DAMAGE
Transition the Conext SW to Standby mode
a
(see page 3–10) before making
changes to the device settings. You may transition the unit back to Operating
mode after enacting the changes.
Failure to follow these instructions can damage equipment.
a.Critical loads will lose power and disconnect from the grid (or generator) when the Conext
SW transitions to Standby mode.
Figure 4-3 Menu Map of the Conext SW Basic Settings
[*Flooded] [Gel] [AGM]
[*250Ah] [50Ah] to [1000Ah]
[*80%] [10%] to [100%]
[*3Stage] or [2StgNoFloat]
[*25.0V] [22.0V]to [29.0V]
[*30.0A] [5.0A]to [30.0A]
[*21.0V] [20.0V]to [24.0V]
CSW4024 00: Basic
Batt Type
Batt Capacity
Max Chg Rate
Charge Cycle
ReCharge Volts
AC In Breaker
Low Batt Cut Out
[Flooded]
[220Ah]
[80%]
[3Stage]
[25.0V]
[30.0A]
[21.0V]
Follow procedures on “To select and change a configurable setting:” on
page 4–4 to change the settings.
Table 4-1 Setting Defaults and Ranges
Model 24-volt Models 48-volt Model
Setting Default Min Max Default Min Max
Batt Type Flooded Flooded, Gel,
AGM, Custom
Flooded Flooded, Gel,
AGM, Custom
Batt Capacity 250Ah 50Ah 100Ah 250Ah 50Ah 1000Ah
Max Chg Rate 100% 10% 100% 100% 10% 100%
Charge Cycle 3Stage 3Stage,
2StgNoFloat
3Stage 3Stage,
2StgNoFloat
ReCharge Volts 25.0V 22.0V 29.0V 50.0V 44.0V 58.0V
AC In Breaker 30A 5A 30A 30A 5A 30A