Conext SW4048 4,000W 48V Installation
Table Of Contents
- Conext™ SW Inverter/Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-03 Revision: Date: 5-2020
- Contact Information solar.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Safety Information
- Precautions When Working With Batteries
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Basic Protection Features
- Grid-interactive and Other Features
- Load Shaving
- AC Support
- Grid-Interactive Delay Feature
- AC Coupling
- AC Couple Smart Charge
- Storing the State of the Inverter Mode
- NoLoadVD
- Low Battery Cut Out Hysteresis
- LBCO Delay
- Lithium Ion Battery Type
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- AC Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Advanced Features Menu
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Configuring Advanced Settings
975-0638-01-03 4–9
Configuring Advanced Settings
Inverter Settings Menu
The Inverter Settings menu contains settings that control when the Conext SW
starts and stops producing AC output.
NOTICE
RISK OF DAMAGE TO CONNECTED DEVICES
The advanced settings are intended for qualified installation/service personnel
only. Before changing advanced settings, you must be familiar with the
settings and the system-wide impact of changing those settings. Setting
parameters incorrectly could damage connected equipment (such as
batteries) or could severely affect the performance of your system. Incorrect
charging configuration can lead to battery damage.
Failure to follow these instructions can result in equipment damage.
NOTICE
EQUIPMENT DAMAGE
Transition the Conext SW to Standby mode (see page 3–10) before making
changes to the device settings. You may transition the unit back to Operating
mode after enacting the changes.
Failure to follow these instructions can damage equipment.
Figure 4-4 Inverter Settings Menu Screen
CSW4024 00: Inv
Low Batt Cut Out
LBCO Hysteresis
LBCO Delay
Hi Batt Cut Out
Search Watts
Search Delay
Inv Block Start
Inv Block Stop
[21.0]
[2.0V]
[10sec]
[29.0V]
[50W]
[2sec]
[hh:mm AM]
[hh:mm AM]
CSW4024 00: Adv
Inverter Settings
Charger Settings
AC Settings
Gen Support
Multi Unit Config
Restore Defaults
Adv Features
[*21.0V] [20.0V] to [24.0V]
[*10sec] [0sec] to [600sec]
[*29.0V] [29.0V] to [34.0V]
[*50W] [5W] to [250W]
[*2sec] [1sec] to [25sec]
[*2.0V] [0.5V] to [5.0V]
Follow procedures on “To select and change a configurable setting:” on page 4–6 to
change the settings.
Table 4-3 Setting Defaults and Ranges
Model 24-volt Models 48-volt Model
Setting Default Min Max Default Min Max
Low Batt Cut
Out
21.0V 20.0V 24.0V 44.0V 40.0V 48.0V
LBCO Hysteresis 2.0V 0.5V 5.0V 2.0V 0.5V 5.0V
LBCO Delay 10sec 0sec 600sec 10sec 0sec 600sec
Hi Batt Cut Out 29.0V 29.0V 34.0V 68.0V 58.0V 68.0V