Conext SW4048 4,000W 48V Installation

Table Of Contents
Configuring Advanced Settings
975-0638-01-03 4–21
NOTE: If a warning is received indicating that a setting is not accepted by the
SCP, gradually increase the value of the setting until the SCP accepts it. This
type of warning means that an internal minimum threshold value is being crossed
and therefore the setting cannot be saved.
Table 4-12 Custom Battery Settings Menu Description
Setting Description
Eqlz Support Enables or disables the ability to enter an equalization cycle.
Refer to the battery manufacturer’s specifications to determine
whether equalization is recommended.
Eqlz
Voltage
a
a.The Eqlz Voltage setting is displayed when Eqlz Support is set to Enabled.
Selects the equalization voltage. Consult your battery
manufacturer for equalization voltage setting.
Bulk Voltage Sets the bulk voltage for a custom battery type. This setting
must be 0.8 V or more for the 48-volt model (or 0.4 or more for
the 24-volt models) than the Bulk Termination Voltage. See note
below.
Bulk
Termination
Voltage
Sets the bulk termination voltage for a custom battery type.
This setting must be 0.8 V or less for the 48-volt model (or 0.4
or less for the 24-volt models) than the Bulk Voltage. See note
below.
Absorb
Voltage
Sets the absorption voltage for a custom battery type.
Float
Voltage
Sets the float voltage for a custom battery type. See note
below.
Batt Temp
Comp
Battery temperature compensation for a custom battery type.
This setting is the reference that the BTS uses to adjust the
charging voltage when the temperature is above or below
77 °F (25 °C).