Conext SW4048 4,000W 48V Installation
Table Of Contents
- Conextâ„¢ SW Inverter/Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-03 Revision: Date: 5-2020
- Contact Information solar.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Safety Information
- Precautions When Working With Batteries
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Basic Protection Features
- Grid-interactive and Other Features
- Load Shaving
- AC Support
- Grid-Interactive Delay Feature
- AC Coupling
- AC Couple Smart Charge
- Storing the State of the Inverter Mode
- NoLoadVD
- Low Battery Cut Out Hysteresis
- LBCO Delay
- Lithium Ion Battery Type
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- AC Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Advanced Features Menu
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Configuration via SCP
4–26 975-0638-01-03
AC Supp Volts
For 48-volt model
Battery voltage threshold in
order to engage regular AC
Support Mode.
53.0V
For 48-volt model
46.0V to 70.0V
cannot be set below
Low Batt Cut Out +
2volts
Load Shave
Enables or disables the load
shaving feature. When in this
mode, the Conext SW operates
until the batteries discharge to
the Low Batt Cut Out
threshold, after which the unit
starts charging the batteries.
The charger is automatically
blocked during the load
shaving time window.
Disabled Disabled,
Enabled
Load Shave
Amps
Sets the maximum amount of
current that can be drawn from
the AC source input by the
loads and battery charger
combined. This setting
determines the amperage level
at which the inverter starts
drawing power from the
batteries to add to the power to
meet load demands. Typically,
this value is set to the peak
usage surcharge threshold
imposed by the utility, if
applicable. See NOTE above.
24A 1A to 24A
LoadShave
Start
Sets the time for when load
shaving is engaged.
12:00 AM
Setting the Load
Shave Start and Load
Shave Stop to the
same time disables
scheduling.
LoadShave
Stop
Sets the time for when load
shaving is disengaged.
12:00 AM
AC Supp on
Soc
Enables or disables the SOC
monitoring for AC Support
Mode.
This setting must be enabled for
AC Supp Start Soc and AC
Supp Stop Soc to take effect.
Enabled Disabled,
Enabled
AC Supp Start
Soc
Sets the high percentage value
of the SOC of the battery for AC
Support Mode to engage.
Applicable only when AC Supp
on Soc is enabled.
80% 70% to 100%
AC Supp Stop
Soc
Sets the low percentage value
of the SOC of the battery for AC
Support Mode to disengage.
Applicable only when AC Supp
on Soc is enabled.
50% 20% to 60%
a.Applies to all Conext SW models.
Table 4-17 AC Support Menu Description and Values
a
Setting Description Default Range