Conext SW4048 4,000W 48V Installation

Table Of Contents
Configuration via SCP
4–26 975-0638-01-03
AC Supp Volts
For 48-volt model
Battery voltage threshold in
order to engage regular AC
Support Mode.
53.0V
For 48-volt model
46.0V to 70.0V
cannot be set below
Low Batt Cut Out +
2volts
Load Shave
Enables or disables the load
shaving feature. When in this
mode, the Conext SW operates
until the batteries discharge to
the Low Batt Cut Out
threshold, after which the unit
starts charging the batteries.
The charger is automatically
blocked during the load
shaving time window.
Disabled Disabled,
Enabled
Load Shave
Amps
Sets the maximum amount of
current that can be drawn from
the AC source input by the
loads and battery charger
combined. This setting
determines the amperage level
at which the inverter starts
drawing power from the
batteries to add to the power to
meet load demands. Typically,
this value is set to the peak
usage surcharge threshold
imposed by the utility, if
applicable. See NOTE above.
24A 1A to 24A
LoadShave
Start
Sets the time for when load
shaving is engaged.
12:00 AM
Setting the Load
Shave Start and Load
Shave Stop to the
same time disables
scheduling.
LoadShave
Stop
Sets the time for when load
shaving is disengaged.
12:00 AM
AC Supp on
Soc
Enables or disables the SOC
monitoring for AC Support
Mode.
This setting must be enabled for
AC Supp Start Soc and AC
Supp Stop Soc to take effect.
Enabled Disabled,
Enabled
AC Supp Start
Soc
Sets the high percentage value
of the SOC of the battery for AC
Support Mode to engage.
Applicable only when AC Supp
on Soc is enabled.
80% 70% to 100%
AC Supp Stop
Soc
Sets the low percentage value
of the SOC of the battery for AC
Support Mode to disengage.
Applicable only when AC Supp
on Soc is enabled.
50% 20% to 60%
a.Applies to all Conext SW models.
Table 4-17 AC Support Menu Description and Values
a
Setting Description Default Range