Conext SW4048 4,000W 48V Installation
Table Of Contents
- Conextâ„¢ SW Inverter/Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-03 Revision: Date: 5-2020
- Contact Information solar.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Safety Information
- Precautions When Working With Batteries
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Basic Protection Features
- Grid-interactive and Other Features
- Load Shaving
- AC Support
- Grid-Interactive Delay Feature
- AC Coupling
- AC Couple Smart Charge
- Storing the State of the Inverter Mode
- NoLoadVD
- Low Battery Cut Out Hysteresis
- LBCO Delay
- Lithium Ion Battery Type
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- AC Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Advanced Features Menu
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Configuring Advanced Settings
975-0638-01-03 4–29
Load Shaving Setting
For Load shaving to be effective, all loads must be connected to the inverter. To
help the batteries supplement the power requirements of the connected load, an
additional source of power (like solar, wind, or hydroelectric) is recommended
but not required.
To demonstrate a scenario where load shaving takes effect on the Conext SW,
the following settings are programmed into the SCP.
Scenario Settings: Load Shave=Enabled
LoadShaveAmps=10A
LoadShaveStart=6:00AM
LoadShaveStop=9:00PM
PLSDelay=Enabled
To use the Load Shaving feature:
1. Enable load shaving.
2. Set the load shaving amps.
3. Set the load shaving start and stop times.
CSW4024 00: AC Support
AC Supp Mode
AC Supp Volts
Load Shave
Load Shave Amps
[Disabled]
[26.0V]
[Enabled]
[24A]
CSW4024 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
Go to Advanced Settings -> AC Support -> Load Shave
Press Enter, then select Enabled using the up and down arrow
buttons. Press Enter.
From AC Support -> Load Shave Amps
Press Enter, then select a value of 10 using
the up and down arrow buttons. Press Enter.
CSW4024 00: AC Support
AC Supp Mode
AC Supp Voltsp
Load Shave
Load Shave Amps
[Enabled]
[Disabled]
[Enabled]
[10A]