Configuring Advanced Settings
975-0638-01-03 4–29
Load Shaving Setting
For Load shaving to be effective, all loads must be connected to the inverter. To
help the batteries supplement the power requirements of the connected load, an
additional source of power (like solar, wind, or hydroelectric) is recommended
but not required.
To demonstrate a scenario where load shaving takes effect on the Conext SW,
the following settings are programmed into the SCP.
Scenario Settings: Load Shave=Enabled
LoadShaveAmps=10A
LoadShaveStart=6:00AM
LoadShaveStop=9:00PM
PLSDelay=Enabled
To use the Load Shaving feature:
1. Enable load shaving.
2. Set the load shaving amps.
3. Set the load shaving start and stop times.
CSW4024 00: AC Support
AC Supp Mode
AC Supp Volts
Load Shave
Load Shave Amps
[Disabled]
[26.0V]
[Enabled]
[24A]
CSW4024 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
Go to Advanced Settings -> AC Support -> Load Shave
Press Enter, then select Enabled using the up and down arrow
buttons. Press Enter.
From AC Support -> Load Shave Amps
Press Enter, then select a value of 10 using
the up and down arrow buttons. Press Enter.
CSW4024 00: AC Support
AC Supp Mode
AC Supp Voltsp
Load Shave
Load Shave Amps
[Enabled]
[Disabled]
[Enabled]
[10A]